C-24BV SERIES

C - 2 4 B V   S E R I E S

ARL Listed - 29707
Zero Clearance - Primary & Secondary Protection
Optional combined electrical supply, fan relay and transformer

Right Side Baffle
Duct Connection 12.13" x 8.88"

C-24BV-KW-Phase @ Volts
1-9KW, 1 or 3 Phase, 208 - 480 Volts

NOTE: Same as C-36BV

FITS

MAGICAIRE
(click here for installation instructions)

24BVX
24BVW

FIRST CO.
(click here for installation instructions)

24CVX
24CVW

AIRTHERM
(click here for installation instructions)

24AVX
24AVW

CALCULATION INFORMATION

SEPARATE HEATER ELECTRICAL SUPPLY:

Heater Amps times 1.25 is minimum circuit ampacity. Minimum circuit ampacity rounded up to the nearest standard protective device rating is maximum circuit protection.

COMBINED ELECTRICAL SUPPLY - COOLING ONLY UNITS:

Heater amps times 1.25 plus 6 is minimum circuit ampacity. Minimum circuit ampacity rounded up the nearest standard protective device rating is maximum circuit protection. COMPARE to Air Conditioners Labe (Write in the LARGER of the two ratings.

COMBINED ELECTRICAL SUPPLY - HEAT PUMPS:

Add heater amps to Heat Pump minimum circuit ampacity for a new total minimum ampacity. Minimum circuit ampacity rounded up to nearest standard protective device rating is maximum circuit protection.

STANDARD PROTECTIVE DEVICE RATINGS:
10, 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90 and 100 amps.

EXAMPLE:

Install a 47.1 amp heater in a heat pump and use combined single electric supply.

If Unit nameplate minimum circuit ampacity 35 - this makes the combined minimum ampacity (35 + 41.7) of 76.7 amps. 76.7 amps rounded up to nearest standard rating (80 amps). The combined maximum protective device is 80 A.