Champion Replacment Parts/Options

NOTE:

Coils and auxiliary switches are available in old and new style.
They are not interchangeable!

Please check the contactor date codes..4 digits denoting week & year. Example: 2392 is Week 23 of 1992.

 
1 Pole, 1 pole w/bus and 2 pole small frames were in a transition period from 2392 to 1693 date codes, some built both ways.

The old style coil is rectangular with double quick connects.

The new  style coil has added "wings" to shield the underside of the contacts from insects. They are not interchangeable!

 
3 Pole, Frames 20 to 40 amps all changed coils with date code 1993 to date.  The new style has "MOD 93" on the label.
There is no real visual difference when installed in the contactor,
but they are not interchangeable!
 
3 Pole, Frames for 50 & 60 Amps became "MOD 93" with date code 1393 to  date. The "old" and new coils are interchangeable! The auxiliaries are  not.

ORDER USING THE FOLLOWING DESCRIPTIONS

COILS

Coils for 23, 25 or 30A1P (& 1PB) - 24 Volts only - Old Style
Coils for 23, 25 or 30A1P (& 1PB) - 24 Volts only - New Style

Coils for 20, 25 or 30A2P & 40A2P2 (24, 120, 240, 277V) Old Style
Coils for 20, 25 or 30A2P & 40A2P2 (24, 120, 240, 277V) New Style

Coils for 20, 25, 30 or 40A2P (24, 120, 240, 277, 480V) Old Style
Coils for 20, 25, 30 or 40A3P "MOD 93") (24, 120, 240, 277, 480, 600V) (36320 Series)

Coils for 50, 60A3P (24, 120, 240, 277, 480V) fits old & new style (35520 Series)
Also for New Series 75 & 90AH

AUXILIARY SWITCHES

20, 25, 30 or 40A3P & 40A2P (SPDT, 10A, 250V) for old style (34220-332)
20, 25, 30 or 40A3P (1NO-1NC, 10A, 600V) for "MOD 93") (34220-332N)

50 or 60A3P (SPDT, 10A, 250V) for old style (34300-332B)
50 or 60A3P (1NO-1NC, 10A, 600V) for "MOD 93" (34300-322)

Auxiliary Switches for 50-60A3P MOD 93 Champion also fit Arrow Hart
75, 90 or 120 AMP MOD 86 Contactors and Model E 30 or 40 AMP 4 Pole